Recommended Insulation R-Values by Climate Zone
ENERGY STAR's recommended attic and floor R-values for each climate zone, what to do about walls, and why blown-in needs both bags and depth.
Updated October 18, 2026
The short answer
ENERGY STAR recommends R-30 in an uninsulated attic in zone 1, R-49 in zones 2–3 and R-60 in zones 4–8. If the attic already has 3–4 in of insulation, the targets for adding more are R-25, R-38 and R-49. The levels are based on the 2021 International Energy Conservation Code (Table R402.1.3).
Recommended R-values by zone
For retrofitting existing wood-framed homes (ENERGY STAR):
| Climate zone | Attic, uninsulated | Attic, 3–4 in existing | Floor |
|---|---|---|---|
| 1 | R-30 | R-25 | R-13 |
| 2 | R-49 | R-38 | R-13 |
| 3 | R-49 | R-38 | R-19 |
| 4A and 4B | R-60 | R-49 | R-19 |
| 4C, 5 and 6 | R-60 | R-49 | R-30 |
| 7 and 8 | R-60 | R-49 | R-38 |
Finding your climate zone
IECC climate zones run from 1 (hot, southern Florida and Hawaii) to 8 (sub-arctic Alaska), and are assigned by county. ENERGY STAR and the Department of Energy publish maps; your building department can also tell you. Zone 4 is split into 4A, 4B and 4C (the marine Pacific Northwest), and the floor recommendation differs between them.
What about walls?
ENERGY STAR doesn’t give one wall R-value for existing homes. Its advice: fill empty wall cavities, and when you replace siding, add insulated sheathing — R-5 in zone 3 and R-5 to R-10 in zones 4–8. For already-insulated 2×4 walls in zones 4–8 it suggests adding R-10 sheathing when re-siding.
R-value, bags and depth
Batts carry their R-value in their thickness — an R-13 batt for a 2×4 wall, R-19 for 2×6, R-30 for attics — so you count bags by area. Loose-fill (blown-in) insulation is different: the bag chart gives both the number of bags per 1,000 sq ft and a minimum thickness for each R-value, and you need both to get the rated R-value. That’s required on the label by the FTC’s R-value Rule.
For example, Owens Corning’s AttiCat PINK chart lists R-49 at 25 bags per 1,000 sq ft and a minimum thickness of 17 in; R-60 at 31.5 bags and 20.5 in. Other products reach the same R-value at different depths and bag counts — always use the chart on the bag you buy.
Worked example: a zone 5 attic
Attic floor 1,000 sq ft, uninsulated → target R-60 Blown-in (AttiCat) R-60: 31.8 sq ft per bag → 1,000 ÷ 31.8 = 31.4 → 32 bags, ≥ 20.5 in deep Or R-49 39.9 sq ft per bag → 1,000 ÷ 39.9 = 25.1 → 26 bags, ≥ 17 in deep
In metric
The figures above are in US units, as the manufacturers and standards give them. Here they are in metric, converted with the same factors the calculators use. Switch any calculator to m · cm to work in metric from the start.
| Figure in this guide | US | Metric |
|---|---|---|
| Existing insulation, 3 in | 3 inches | ≈ 76 mm |
| Existing insulation, 4 in | 4 inches | ≈ 102 mm |
R-values are quoted in US units. Metric markets use RSI (m²·K/W), a different scale, so use the RSI printed on a metric product rather than converting by hand.
Calculate it for your project
The Insulation Calculator looks up the recommendation for your zone and counts batts or blown-in bags from the coverage chart. The attic insulation planner adds air-sealing supplies and cost.